FD 60 C3-Q

Diesel generators 22.0 kVA - 66.0 kVA

Ask about this generator

Contact us

Features of the unit

Engine Cummins 4BTAA3.3-G14
Exhaust emissions stage IIIA
Fuel system direct injection
Speed regulation ECU
Frequency 50Hz
ESP maximum power 66.0 kVA / 53.0 kW
PRP rated power 60.0 kVA / 48.0 kW
Fuel tank 330 l
Alternator Linz PRO18L G/4
Performance class G2 (wg ISO 8528-5)

Characteristics

  • Digital voltage regulation +/- 0,25 %
  • Low disturbance level THD <3%
  • Alternator short circuit capacity 300% 10s % ln
  • Class H insulation
  • Protection index IP23
  • Performance class G2 (according to ISO 8528-5)
  • Ready to load just after start
  • AMF and MRS functionality and protection
  • Autonomy 49.5 h with 75 % load
  • Stage IIIA emission standard

Unit Specification Sheet

FD 60 C3-Q

This generator is also available in an open-frame version (without canopy). Please contact us for detailed information.

Contact us

ComAp driver

InteliLite AMF 25

Controller type: ComAp InteliLite AMF 25
Support of Dual AMF/MRS applications
Direct communication with EFI engines
Total remote monitoring and control
Intuitive operator interface, adjustable Main Screen
Real time clock
Comprehensive history log with up to 350 events
3 phase true RMS current and voltage measurement
Both mains and generator voltage detection
Active/Reactive Power and Power Factor per phase measurement
Run Hours counter with source selector
3 maintenance timers (counting even under zero)
Multipurpose flexible timers (also for rental)
Battery voltage measurement
Complete engine and alternator protection
CAN modules support
USB port on-board
2 slots for plug-in modules
Plug-in module concept for more capabilities (RS232, RS485, Ethernet, GPRS, 4G/LTE, Modbus, SNMP, emails, SMS, I/Os)
Cloud-based monitoring and control via WebSupervisor) (optional module required)
Geofencing and tracking via WebSupervisor (optional module required)
Control and monitoring over SMS (GSM module required)
3 levels of password protection
In-built PLC, complemented with a monitoring/debugging tool, for additional functionality, if required
Spare inputs and outputs available by default: binary input – 2, binary output – 1, analogue input – 3
A version for low temperature is also available

Cummins engine

4BTAA3.3-G14

Manufacturer Cummins
Type 4BTAA3.3-G14
Made in Indie
Engine Power 56,0 kW
Emission standard stage IIIA
Rotation per minute 1500 rpm
Engine governor ECU
Governor class G2 (wg ISO 8528-5)
Displacement 3,3 l
No of cylinder 4
Fuel system direct injection
Electrical system 12 V
Cooling system capacity 13,0 l
Oil pan capacity 7,9 l
Fuel type Diesel (EN 590)

Linz alternator

PRO18L G/4

Manufacturer Linz
Type PRO18L G/4
Made in Italy
Nominal voltage 400 V
Nominal power factor (cos φ) 0,8
Ambient temperature, altitude 40 ºC, 1000m n.p.m.
Nominal Power 60.0 kVA
Protection index IP 23
No of bearing single bearing
Coupling direct
Technology brushless
Short circuit maintaining capacity 300% 10s
Efficiency 89,6 %
Insulation class H
Total harmonic content THD <3 %
Reactance Xd'' 7 %
Voltage regulator type AVR HVR-11
Voltage measurement 3 phases
Voltage accuracy +/- 0,25 %
AVR supply system Auxiliary winding
Share by: